Digital Input Module Allen-Bradley Ex I/O 1718-IBN8B

1718 Ex I/O digital input module, 8 channels, NAMUR sensor or volt-free contact inputs, line fault detection, RIUP, Zone 1 enclosure installation
Lifecycle Status: Active

Description

The Allen-Bradley 1718-IBN8B Ex I/O digital input module is designed for hazardous-area distributed I/O applications that require eight intrinsically safe digital input channels for NAMUR sensors or volt-free contacts. It is used within the 1718 Ex I/O platform for process and machine control architectures where field signals are brought into a higher-level EtherNet/IP-based control system through the system adapter.

Lifecycle Status: Active

  • 1718 Ex I/O digital input module
  • 8 digital input channels
  • Supports NAMUR sensors and volt-free contacts
  • Inputs rated according to EN 60947-5-6 (NAMUR)
  • Switching point / hysteresis: 1.2…2.1 mA / ±0.2 mA
  • Internal resistor: 1 kΩ
  • Line fault detection configurable per channel through the Add-on Profile
  • Module can be removed and inserted under power (RIUP)
  • Permanently self-monitoring design
  • Inputs Ex ia
  • For installation in suitable enclosures in Zone 1
  • Uses chassis bus connection with 1718 system architecture
  • Occupied slots: 2
  • Power consumption: 1.0 W
  • Power dissipation: 1.0 W

This module fits industrial automation applications that need intrinsically safe digital signal acquisition from hazardous locations, including process skids, chemical handling systems, and remote field instrumentation panels. Within a 1718 Ex I/O station, it provides a practical interface for digital field devices while supporting maintainability and fault diagnostics in demanding environments.